User Manual

11 / 16
Siemens Control device PN40, safety function to DIN EN 14597 CE1N4388en
Smart Infrastructure 2020-01-09
Cylinder with valve
stem connector
fully retracted
stroke = 0%
4564Z12
0
1
Cylinder with valve
stem connector
fully extended
stroke = 100 %
4564Z13
0
1
The control device can only be operated in auto-
matic mode. The crank (2) on the manual adjust-
ment knob (1) is engaged and secured with anti-
tamper screws.
When removing anti-tamper screws (3) TÜV ap-
proval for the safety function to DIN EN 14597
ceases.
1
2
4387Z14
3
Engaged crank (2) on the
manual adjustment knob (1)
Maintenance notes
The MK..6.. control devices are maintenance-free
When servicing the control device:
Never disassemble valve and actuator for maintenance or servicing else
TÜV approval for the safety function to DIN EN 14597 ceases.
Switch off pump of the hydronic loop
Interrupt the power supply to the actuator
Close the main shutoff valves in the system
Release pressure in the pipes and allow them to cool down completely
If necessary, disconnect electrical connections from the terminals
Recommendation MK..662..: Trigger stroke calibration after servicing or mainte-
nance.
The control device has to be replaced as a whole unit else TÜV approval for the
safety function to DIN EN 14597 ceases.
A damaged housing or cover represents an injury risk.
NEVER uninstall an actuator from the valve.
Uninstall the valve-actuator combination (actuating device) as a complete
device.
Use only properly trained technicians to uninstall the unit.
Send the actuating device together with an error report to your local Sie-
mens representative for analysis and disposal.
Properly mount the new actuating device (valve and actuator).
Parts could fly ultimately resulting in injuries from uninstalling an actuator with a
damaged valve housing due to the tensioned return spring.
It is not permitted to replace the sealing glands. In case of leakages, the control
device has to be replaced as a whole unit else TÜV approval for the safety function
to DIN EN 14597 ceases.
Automatic operation
Repair
Warning
Sealing gland