User Manual

9 / 14
Siemens Control device PN25, safety function to DIN EN 14597 CE1N4389en
Building Technologies 10.01.2011
Commissioning notes
The manual adjuster must remain secured with anti-tamper screws as factory
delivered.
When removing anti-tamper screws TÜV approval for the safety function to
DIN EN 14597 ceases.
Valve stem retracts: valve opens = increasing flow
Valve stem extends: valve closes = decreasing flow
When commissioning the system, check the wiring and functions, and set any aux-
iliary switches and potentiometers as necessary, or check the existing settings.
The actuator is driven to OPEN (valve open) until the red clamp, that fixes a stroke
position of ca. 50 % can be easily removed. Voltage must be applied to either ter-
minal 21 and Y1 to drive to OPEN, or voltage to G-G0 as well as Y > 70 %.
The safety function is only enabled after the red safety clamp is removed.
Cylinder with valve
stem connector
fully retracted
stroke = 0%
4564Z12
0
1
Cylinder with valve
stem connector
fully extended
stroke = 100 %
4564Z13
0
1
The control device can only be operated in auto-
matic mode. The crank (2) on the manual adjust-
ment knob (1) is engaged and secured with anti-
tamper screws.
When removing anti-tamper screws TÜV approval
for the safety function to DIN EN 14597 ceases.
1
2
4564Z14
Engaged crank
(2) on the
manual adjustment knob
(1)
Maintenance notes
The MK..5..G control devices are maintenance-free
When servicing the control device:
Never disassemble valve and actuator for maintenance or servicing else
TÜV approval for the safety function to DIN EN 14597 ceases.
Switch off pump of the hydronic loop
Interrupt the power supply to the actuator
Close the main shutoff valves in the system
Release pressure in the pipes and allow them to cool down completely
If necessary, disconnect electrical connections from the terminals
Recommendation MKB562..G: Trigger stroke calibration after servicing or mainte-
nance.
The control device has to be replaced as a whole unit else TÜV approval for the
safety function to DIN EN 14597 ceases.
MKB..
Automatic operation
Repair