User Manual
5 / 14
Siemens Control device PN25, safety function to DIN EN 14597 CE1N4389en
Building Technologies 10.01.2011
Override control input can be operated in following different modes of operation
Z-mode
no function fully open closed override with 0…1000 Ω
Connections Transfer
linear or equal-percentage linear or equal-percentage
• Z-contact not connected
• Valve stroke follows Y-
input
• Z-contact connected
directly to G
• Y-input has no effect
• Z-contact connected
directly to G0
• Y-input has no effect
• Z-contact connected to M
via resistor R
• Starting position at 50 /
end position at 900
• Y-input has no effect
Shown operation modes are based on the factory setting «direct acting»
Y-input has no effect in Z-mode.
Accessories
ASC9.3
double auxiliary switch
ASZ7.3..
potentiometer
adjustable switching points ASZ7.3: 0…1000
ASZ7.31: 0…135
ASZ7.32: 0…200
ASC1.6
Auxiliary switch
Switching point 0...5 % stroke
Override control
input Z
MKB562..G
Note
MKB532..G
MKB562..G