Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
95
P2101[3] Stop reaction value
Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALARMS Active: first confirm QuickComm. No Max: 4
Sets drive stop reaction values for fault selected by P2100 (alarm number stop reaction).
This indexed parameter specifies the special reaction to the faults/warnings defined in P2100 indices 0 to 2.
Possible Settings:
0 No reaction, no display
1 OFF1 stop reaction
2 OFF2 stop reaction
3 OFF3 stop reaction
4 No reaction warning only
Index:
P2101[0] : Stop reaction value 1
P2101[1] : Stop reaction value 2
P2101[2] : Stop reaction value 3
Note:
Settings 0 - 3 only are available for fault codes.
Settings 0 and 4 only are available for warnings.
Index 0 (P2101) refers to fault/warning in index 0 (P2100).
P2103 BI: 1. Faults acknowledgement Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 722:2
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines first source of fault acknowledgement, e.g. keypad/DIN, etc. (depending on setting).
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
P2104 BI: 2. Faults acknowledgement Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Selects second source of fault acknowledgement.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
P2106 BI: External fault Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Selects source of external faults.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
r2110[4] Warning number Min: -
Datatype: U16 Unit: - Def: -
P-Group: ALARMS Max: -
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warnings (indices 2 and 3) may be
viewed.
Index:
r2110[0] : Recent Warnings --, warning 1
r2110[1] : Recent Warnings --, warning 2
r2110[2] : Recent Warnings -1, warning 3
r2110[3] : Recent Warnings -1, warning 4
Note:
The keypad will flash while a warning is active. The LEDs indicate the warning status in this case.
If an AOP is in use, the display will show number and text of the active warning.
Notice:
Indices 0 and 1 are not stored.
Level:
3
Level:
3
Level:
3
Level:
3
Level:
2