Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
94 6SE6400-5BA00-0BP0
r2090 BO: Control word 1 from CB Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays control word 1 received from communication board (CB).
Bitfields:
Bit00 ON/OFF1 0 NO
1 YES
Bit01 OFF2: Electrical stop 0 YES
1NO
Bit02 OFF3: Fast stop 0 YES
1NO
Bit03 Pulse enable 0 NO
1 YES
Bit04 RFG enable 0 NO
1 YES
Bit05 RFG start 0 NO
1 YES
Bit06 Setpoint enable 0 NO
1 YES
Bit07 Fault acknowledge 0 NO
1 YES
Bit08 JOG right 0 NO
1 YES
Bit09 JOG left 0 NO
1 YES
Bit10 Control from PLC 0 NO
1 YES
Bit11 Reverse (setpoint inversion) 0 NO
1 YES
Bit13 Motor potentiometer MOP up 0 NO
1 YES
Bit14 Motor potentiometer MOP down 0 NO
1 YES
Bit15 Local / Remote 0 NO
1 YES
Note:
If P700 = 6 (Profibus) then P810 must be set to 2090.15 for correct operation. This will not be cleared
automatically when P700 is no longer equal to 6.
Details:
See relevant communication board manual for protocol definition and appropriate settings.
r2091 BO: Control word 2 from CB Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays control word 2 received from communication board (CB).
Bitfields:
Bit00 Fixed frequency Bit 0 0 NO
1 YES
Bit01 Fixed frequency Bit 1 0 NO
1 YES
Bit02 Fixed frequency Bit 2 0 NO
1 YES
Bit08 PID enabled 0 NO
1 YES
Bit09 DC brake enabled 0 NO
1 YES
Bit13 External fault 1 0 YES
1NO
Details:
See relevant communication board manual for protocol definition and appropriate settings.
P2100[3] Alarm number selection Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALARMS Active: first confirm QuickComm. No Max: 65535
Selects up to 3 faults or warnings for non-default reactions.
Index:
P2100[0] : Fault Number 1
P2100[1] : Fault Number 2
P2100[2] : Fault Number 3
Example:
If you want F0005 to perform an OFF3 instead of an OFF2, set P2100[0] = 5, then select the desired
reaction in P2101[0] (in this case, set P2101[0] = 3).
Note:
All fault codes have a default reaction to OFF2. Some fault codes caused by hardware trips (e.g.
overcurrent) cannot be changed from the default reactions.
Level:
3
Level:
3
Level:
3