Operating instructions
04/02     1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
91
r2037 BO: CtrlWrd2 from COM link (USS)
Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays control word 2 from COM link (i.e. word 4 within USS).
Bitfields:
Bit00 Fixed frequency Bit 0 0 NO
1 YES
Bit01 Fixed frequency Bit 1 0 NO
1 YES
Bit02 Fixed frequency Bit 2 0 NO
1 YES
Bit08 PID enabled 0 NO
1 YES
Bit09 DC brake enabled 0 NO
1 YES
Bit13 External fault 1 0 YES
1NO
Details:
See r2033 (control word 2 from BOP link).
P2040 CB telegram off time Min: 0
CStat: CT Datatype: U16 Unit: ms Def: 0
P-Group: COMM Active: Immediately QuickComm. No Max: 65535
Defines time after which a fault will be generated (F0070) if no telegram is received via the link.
Dependency:
Setting 0 = watchdog disabled
P2041[5] CB parameter Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: COMM Active: first confirm QuickComm. No Max: 65535
Configures a communication board (CB).
Index:
P2041[0] : CB parameter 0
P2041[1] : CB parameter 1
P2041[2] : CB parameter 2
P2041[3] : CB parameter 3
P2041[4] : CB parameter 4
Details:
See relevant communication board manual for protocol definition and appropriate settings.
Level:
3
Level:
3
Level:
3