Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
86 6SE6400-5BA00-0BP0
P2014[2] USS telegram off time Min: 0
CStat: CT Datatype: U16 Unit: ms Def: 0
P-Group: COMM Active: Immediately QuickComm. No Max: 65535
Defines a time T_off after which a fault will be generated (F0070) if no telegram is received via the USS
channels.
Index:
P2014[0] : Serial interface COM link
P2014[1] : Serial interface BOP link
Notice:
By default (time set to 0), no fault is generated (i.e. watchdog disabled).
r2015[4] CO: PZD from BOP link (USS) Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays process data received via USS on BOP link (RS232 USS).
STX
LGE
ADR
Start of text
Length
Address
PKW
PZD
BCC
Parameter ID value
Process data
Block check character
USS telegram
PZD mapping to parameter r2015
r2033
r2032
STW
HSW
Control word
Main setpoint
USS on BOP link
[0]
r2015
[1]
[2]
[3]
STXLGEADRBCC
PZD1
STW1
PZD2
HSW
PZD3PZD4
STW2
P2012
Parameter
Process data
PKWPZD
Index:
r2015[0] : Received word 0
r2015[1] : Received word 1
r2015[2] : Received word 2
r2015[3] : Received word 3
Note:
The control words can be viewed as bit parameters r2032 and r2033.
Level:
3
Level:
3