MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
77
P1316 Boost end frequency
Min: 0.0
CStat: CUT Datatype: Float Unit: % Def: 20.0
P-Group: CONTROL Active: Immediately QuickComm. No Max: 100.0
Defines point at which programmed boost reaches 50 % of its value.
This value is expressed in [%] relative to P0310 (rated motor frequency).
The default frequency is defined as follows:
)3
P
153
(  2 = f
motor
min Boost +⋅
Note:
The expert user may change this value to alter the shape of the curve, e.g. to increase torque at a particular
frequency.
Default value is dependant on inverter rated power.
Details:
See diagram in P1310 (continuous boost).
P1320 Programmable V/f freq. coord. 1 Min: 0.00
CStat: CT Datatype: Float Unit: Hz Def: 0.00
P-Group: CONTROL Active: Immediately QuickComm. No Max: 650.00
Sets V/f coordinates (P1320/1321 to P1324/1325) to define V/f characteristic.
V
P1325
f1
P1320
fmax
P1082
V
max
r0071
P0304
P1323
P1321
P1310
f0
0 Hz
f2
P1322
f3
P1324
fn
P0310
f
]P0304[V
100[%]
r0395[%]
100[%]
P1310[%]
P1310[V] ⋅⋅=
V
max
 = f(V
dc
, M
max
)
Example:
This parameter can be used to provide correct torque at correct frequency and is useful when used with
synchronous motors.
Dependency:
To set parameter, select P1300 = 3 (V/f with programmable characteristic).
Note:
Linear interpolation will be applied between the individual data points.
V/f with programmable characteristic (P1300 = 3) has 3 programmable points. The two non-programmable
points are:
- Continuous boost P1310 at zero 0 Hz
- Rated motor voltage P0304 at rated motor frequency P0310
The acceleration boost and starting boost defined in P1311 and P1312 are applied to V/f with
programmable characteristic.
P1321 Programmable V/f volt. coord. 1 Min: 0.0
CStat: CUT Datatype: Float Unit: V Def: 0.0
P-Group: CONTROL Active: Immediately QuickComm. No Max: 3000.0
See P1320 (programmable V/f freq. coord. 1).