MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
73
P1300 Control mode
Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: CONTROL Active: first confirm QuickComm. Yes Max: 3
Controls relationship between speed of motor and voltage supplied by inverter as illustrated in the diagram
below.
Vn
0
fn
V
f
'0'
'2'
Possible Settings:
0   V/f with linear characteristic
1   V/f with FCC
2   V/f with parabolic characteristic
3   V/f with programmable characteristic
Note:
V/f mode:
P1300 = 1 : V/f with FCC (flux current control)
* Maintains motor flux current for improved efficiency.
* If FCC is chosen, linear V/f is active at low frequencies.
P1300 = 2 : V/f with a quadratic curve
* Suitable for centrifugal fans / pumps
The following table presents an overview of control parameters (V/f) that can be modify in relationship to
P1300 dependencies:
ParNo. ParText Level U/f
P1300 = 0 1 2 3
P1300 Control mode 2 xxxx
P1310 Continuous boost 2 xxxx
P1311 Acceleration boost 2 xxxx
P1312 Starting boost 2 xxxx
P1316 Boost end frequency 3 xxxx
P1320 Programmable V/f freq. coord. 1 3
−−−
x
P1321 Programmable V/f volt. coord. 1 3
−−−
x
P1322 Programmable V/f freq. coord. 2 3
−−−
x
P1323 Programmable V/f volt. coord. 2 3
−−−
x
P1324 Programmable V/f freq. coord. 3 3
−−−
x
P1325 Programmable V/f volt. coord. 3 3
−−−
x
P1333 Start frequency for FCC 3
−
x
−−
P1335 Slip compensation 2 xxxx
P1336 Slip limit 2 xxxx
P1338 Resonance damping gain V/f 3 xxxx
P1340 Imax controller prop. gain 3 xxxx
P1341 Imax controller integral time 3 xxxx
P1345 Imax controller prop. gain 3 xxxx
P1346 Imax controller integral time 3 xxxx
P1350 Voltage soft start 3 xxxx