P1211 Number of restart attempts
Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 3
P-Group: FUNC Active: first confirm QuickComm. No Max: 10
Specifies number of times inverter will attempt to restart if automatic restart P1210 is activated.
P1215 Holding brake enable Min: 0
CStat: T Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm. No Max: 1
Enables/disables holding brake function. This function applies the following profile to the inverter:
Relay switching is also possible at point 1 and point 2 (if programmed in P0731 = 52.C) to control a brake.
fmin
(P1080)
P1216
OFF1/OFF3
ON
t
ON / OFF2:
0
1
t
r0052.C
t
f
t
OFF2
0t
fmin
(P1080)
P1217P1216
OFF1/OFF3
ON
t
ON / OFF1/OFF3:
1
r0052.C
t
f
Point 2Point 1
inactive
active
Possible Settings:
0 Motor holding brake disabled
1 Motor holding brake enabled
Note:
The brake relay opens at point 1, if enabled using P0731 (function of digital output), and closes at point 2.
Level:
3
Level:
2