Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
63
P1135 OFF3 ramp-down time
Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 5.00
P-Group: SETPOINT Active: first confirm QuickComm. Yes Max: 650.00
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
Note:
This time may be exceeded if the VDC_max. level is reached.
P1140 BI: RFG enable Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of RFG enable command (RFG: ramp function generator). If binary input is equal
to zero than the RFG output will be set immediately to 0.
P1141 BI: RFG start Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of RFG start command (RFG: ramp function generator). If binary input is equal to
zero than the RFG output is held at it present value.
P1142 BI: RFG enable setpoint Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of RFG enable setpoint command (RFG: ramp function generator). If binary input
is equal to zero than the RFG input will be set to zero and the RFG output will be ramp-down to zero.
r1170 CO: Frequency setpoint after RFG Min: -
Datatype: Float Unit: Hz Def: -
P-Group: SETPOINT Max: -
Displays overall frequency setpoint after ramp generator.
Level:
2
Level:
4
Level:
4
Level:
4
Level:
3