Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
58 6SE6400-5BA00-0BP0
P1091 Skip frequency 1 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines skip frequency 1 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).
P1101
P1091
f in
f out
Skip frequency
bandwidth
Skip frequency
Notice:
Stationary operation is not possible within the suppressed frequency range; the range is merely passed
through (on the ramp).
For example, if P1091 = 10 Hz and P1101 = 2 Hz, it is not possible to operate continuously between 10 Hz
+/- 2 Hz (i.e. between 8 and 12 Hz).
P1092 Skip frequency 2 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines skip frequency 2 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).
Details:
See P1091 (skip frequency 1).
P1093 Skip frequency 3 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines skip frequency 3 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).
Details:
See P1091 (skip frequency 1).
P1094 Skip frequency 4 Min: 0.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines skip frequency 4 which avoids effects of mechanical resonance and suppresses frequencies within
+/- P1101 (skip frequency bandwidth).
Details:
See P1091 (skip frequency 1).