Operating instructions
04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
55
P1071 CI: Main setpoint scaling
Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 4000:0
Defines source of the main setpoint scaling.
Common Settings:
755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint
P1074 BI: Disable additional setpoint Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Disables additional setpoint
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
P1075 CI: Additional setpoint Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 4000:0
Defines source of the additional setpoint (to be added to main setpoint).
Common Settings:
755 = Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint
P1076 CI: Additional setpoint scaling Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 1:0
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 4000:0
Defines source of scaling for additional setpoint (to be added to main setpoint).
Common Settings:
1 = Scaling of 1.0 (100%)
755 = Analog input 1 Setpoint
1024 = Fixed Frequency Setpoint
1050 = MOP Setpoint
r1078 CO: Total frequency setpoint Min: -
Datatype: Float Unit: Hz Def: -
P-Group: SETPOINT Max: -
Displays sum of main and additional setpoints in [Hz].
r1079 CO: Selected frequency setpoint Min: -
Datatype: Float Unit: Hz Def: -
P-Group: SETPOINT Max: -
Displays selected frequency setpoint.
Following frequency setpoints are displayed:
r1078 Total frequency setpoint
P1058 JOG frequency right
P1059 JOG frequency left
Dependency:
P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.
Note:
P1055 = 0 and P1056 = 0 ==> Total frequency setpoint is selected.
Level:
3
Level:
3
Level:
3
Level:
3
Level:
3
Level:
3