Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
54 6SE6400-5BA00-0BP0
P1060 JOG ramp-up time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 10.00
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 650.00
Sets jog ramp-up time. This is the time used while jogging is active.
f (Hz)
0
f max
(P1082)
P1060
t (s)
Notice:
Ramp times will be used as follows:
P1060 / P1061 :  JOG mode is active
P1120 / P1121 : Normal mode (ON/OFF) is active
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
P1061 JOG ramp-down time Min: 0.00
CStat: CUT Datatype: Float Unit: s Def: 10.00
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 650.00
Sets ramp-down time. This is the time used while jogging is active.
f (Hz)
0
f max
(P1082)
P1061
t (s)
Notice:
Ramp times will be used as follows:
P1060 / P1061 :  JOG mode is active
P1120 / P1121 : Normal mode (ON/OFF) is active
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
P1070 CI: Main setpoint Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 755:0
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 4000:0
Defines source of main setpoint.
Common Settings:
755 =  Analog input 1 setpoint
1024 = Fixed frequency setpoint
1050 = Motor potentiometer (MOP) setpoint
Level:
2
Level:
2
Level:
3