Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
52 6SE6400-5BA00-0BP0
P1036 BI: Enable MOP (DOWN-command) Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 19:14
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source for motor potentiometer setpoint decrease frequency.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
19.E = MOP down via BOP
P1040 Setpoint of the MOP Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 5.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Determines setpoint for motor potentiometer control (P1000 = 1).
Note:
If motor potentiometer setpoint is selected either as main setpoint or additional setpoint, the reverse
direction will be inhibited by default of P1032 (inhibit reverse direction of MOP).
To re-enable reverse direction, set P1032 = 0.
r1050 CO: Act. Output freq. of the MOP Min: -
Datatype: Float Unit: Hz Def: -
P-Group: SETPOINT Max: -
Displays output frequency of motor potentiometer setpoint ([Hz]).
P1120
f
P1080
"1"
"0"
"1"
"0"
t
t
t
DIN
BOP
USS
BOP link
USS
COM link
CB
COM link
"1"
"0"
t
P1082
P1121
P1035
P1036
P0840
-P1080
r1050
f
act
-P1082
P1055 BI: Enable JOG right Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source of JOG right when P0719 = 0 (remote selection of command/setpoint source).
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
19.8 = JOG right via BOP
Level:
3
Level:
2
Level:
3
Level:
3