Operating instructions

MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
50 6SE6400-5BA00-0BP0
P1004 Fixed frequency 4 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 15.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 4.
Details:
See parameter P1001 (fixed frequency 1).
P1005 Fixed frequency 5 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 20.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 5.
Details:
See parameter P1001 (fixed frequency 1).
P1006 Fixed frequency 6 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 25.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 6.
Details:
See parameter P1001 (fixed frequency 1).
P1007 Fixed frequency 7 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 30.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 7.
Details:
See parameter P1001 (fixed frequency 1).
P1016 Fixed frequency mode - Bit 0 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1016 defines the mode of selection
Bit 0.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
P1017 Fixed frequency mode - Bit 1 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1017 defines the mode of selection
Bit 1.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
P1018 Fixed frequency mode - Bit 2 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: SETPOINT Active: first confirm QuickComm. No Max: 3
Fixed frequencies can be selected in three different modes. Parameter P1018 defines the mode of selection
Bit 2.
Possible Settings:
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
Details:
See table in P1001 (fixed frequency 1) for description of how to use fixed frequencies.
Level:
2
Level:
2
Level:
2
Level:
2
Level:
3
Level:
3
Level:
3