Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
49
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
P1000 =
1
2
Additonal
setpoint
P1000 = 1
2
Main
setpoint
Setpoint
channel
Motor
control
Note:
Single digits denote main setpoints that have no additional setpoint.
P1001 Fixed frequency 1 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 0.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 1.
There are 3 types of fixed frequencies:
1. Direct selection
2. Direct selection + ON command
3. Binary coded selection + ON command
1. Direct selection (P0701 - P0703 = 15):
In this mode of operation 1 digital input selects 1 fixed frequency.
If several inputs are active together, the selected frequencies are summed.
E.g.: FF1 + FF2 + FF3.
2. Direct selection + ON command (P0701 - P0703 = 16):
The fixed frequency selection combines the fixed frequencies with an ON command.
In this mode of operation 1 digital input selects 1 fixed frequency.
If several inputs are active together, the selected frequencies are summed.
E.g.: FF1 + FF2 + FF3.
3. Binary coded selection + ON command (P0701 - P0703 = 17):
Up to 7 fixed frequencies can be selected using this method.
The fixed frequencies are selected according to the following table:
Example:
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Active
ActiveActive
Active
Active
Active
Active
Active
Active
Active
Active
Active
Inactive
Inactive
Inactive
Inactive
DIN3 DIN2 DIN1
OFF
P1001 FF1
P1002 FF2
P1003 FF3
P1004 FF4
P1005 FF5
P1006 FF6
P1007 FF7
Dependency:
Select fixed frequency operation (using P1000).
Inverter requires ON command to start in the case of direct selection (P0701 - P0706 = 15).
Note:
Fixed frequencies can be selected using the digital inputs, and can also be combined with an ON command.
P1002 Fixed frequency 2 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 5.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 2.
Details:
See parameter P1001 (fixed frequency 1).
P1003 Fixed frequency 3 Min: -650.00
CStat: CUT Datatype: Float Unit: Hz Def: 10.00
P-Group: SETPOINT Active: Immediately QuickComm. No Max: 650.00
Defines fixed frequency setpoint 3.
Details:
See parameter P1001 (fixed frequency 1).
Level:
2
Level:
2
Level:
2