Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
47
P0970 Factory reset
Min: 0
CStat: C Datatype: U16 Unit: - Def: 0
P-Group: PAR_RESET Active: first confirm QuickComm. No Max: 1
P0970 = 1 resets all parameters to their default values.
Possible Settings:
0 Disabled
1 Parameter reset
Dependency:
First set P0010 = 30 (factory settings).
Stop drive (i.e. disable all pulses) before you can reset parameters to default values.
Note:
The following parameters retain their values after a factory reset:
P0014 Store mode
r0039 CO: Energy consumption meter [kWh]
P0100 Europe / North America
P0918 CB address
P2010 USS baud rate
P2011 USS address
P0971 Transfer data from RAM to EEPROM Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: COMM Active: first confirm QuickComm. No Max: 1
Transfers values from RAM to EEPROM when set to 1.
Possible Settings:
0 Disabled
1 Start transfer
Note:
All values in RAM are transferred to EEPROM.
Parameter is automatically reset to 0 (default) after successful transfer.
Level:
1
Level:
3