Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
46 6SE6400-5BA00-0BP0
r0967 Control word 1 Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays control word 1.
Bitfields:
Bit00 ON/OFF1 0 NO
1 YES
Bit01 OFF2: Electrical stop 0 YES
1NO
Bit02 OFF3: Fast stop 0 YES
1NO
Bit03 Pulse enable 0 NO
1 YES
Bit04 RFG enable 0 NO
1 YES
Bit05 RFG start 0 NO
1 YES
Bit06 Setpoint enable 0 NO
1 YES
Bit07 Fault acknowledge 0 NO
1 YES
Bit08 JOG right 0 NO
1 YES
Bit09 JOG left 0 NO
1 YES
Bit10 Control from PLC 0 NO
1 YES
Bit11 Reverse (setpoint inversion) 0 NO
1 YES
Bit13 Motor potentiometer MOP up 0 NO
1 YES
Bit14 Motor potentiometer MOP down 0 NO
1 YES
Bit15 Local / Remote 0 NO
1 YES
r0968 Status word 1 Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMM Max: -
Displays active status word of inverter (in binary) and can be used to diagnose which commands are active.
Bitfields:
Bit00 Drive ready 0 NO
1 YES
Bit01 Drive ready to run 0 NO
1 YES
Bit02 Drive running 0 NO
1 YES
Bit03 Drive fault active 0 NO
1 YES
Bit04 OFF2 active 0 YES
1NO
Bit05 OFF3 active 0 YES
1NO
Bit06 ON inhibit active 0 NO
1 YES
Bit07 Drive warning active 0 NO
1 YES
Bit08 Deviation setpoint / act. value 0 YES
1NO
Bit09 PZD control 0 NO
1 YES
Bit10 Maximum frequency reached 0 NO
1 YES
Bit11 Warning: Motor current limit 0 YES
1NO
Bit12 Motor holding brake active 0 NO
1 YES
Bit13 Motor overload 0 YES
1NO
Bit14 Motor runs right 0 NO
1 YES
Bit15 Inverter overload 0 YES
1NO
Level:
3
Level:
3