P0781 Width of DAC deadband
Min: 0
CStat: CUT Datatype: Float Unit: - Def: 0
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 20
Sets width of dead-band in [mA] for analog output.
20
P0780
y
2
P0778
y
1
P0777
x
1
P0779
x
2
100 %
mA
P0781
%
P0800 BI: Download parameter set 0 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source of command to start download of parameter set 0 from attached AOP. The first three digits
describe the parameter number of the command source, the last digit refers to the bit setting for that
parameter.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
Note:
Signal of digital input:
0 = No download
1 = Start download parameter set 0 from AOP.
P0801 BI: Download parameter set 1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines sources of command to start download of parameter set 1 from attached AOP. The first three digits
describe the parameter number of the command source, the last digit refers to the bit setting for that
parameter.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
Note:
Signal of digital input:
0 = No download
1 = Start download parameter set 1 from AOP.
P0840 BI: ON/OFF1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 722:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Allows ON/OFF1 command source to be selected using BICO. The first three digits describe the parameter
number of the command source; the last digit denotes the bit setting for that parameter.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
19.0 =  ON/OFF1 via BOP
Dependency:
Active only when P0719 = 0 (remote selection of command/setpoint source).
BICO requires P0700 set to 2 (enable BICO).
The default setting (ON right) is digital input 1 (722.0). Alternative source possible only when function of
digital input 1 is changed (via P0701) before changing value of P0840.