Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
37
P0757 Value x1 of ADC scaling [V]
Min: 0
CStat: CUT Datatype: Float Unit: V Def: 0
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 10
Parameters P0757 - P0760 configure the input scaling as shown in the diagram:
4000H 10 V
ASPmax
100 %
10 V
V
x
100%
%
P0760
P0758
P0757
P0759
P0761 = 0
ASPmin
Where:
Analog setpoints represent a [%] of the normalized frequency in P2000.
Analog setpoints may be larger than 100 %.
ASPmax represents highest analog setpoint (this may be at 10 V).
ASPmin represents lowest analog setpoint (this may be at 0 V).
Default values provide a scaling of 0 V = 0 %, and 10 V = 100 %.
Notice:
The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757.
P0758 Value y1 of ADC scaling Min: -99999.9
CStat: CUT Datatype: Float Unit: % Def: 0.0
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 99999.9
Sets value of Y1 in [%] as described in P0757 (ADC scaling)
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to
be generated.
P0759 Value x2 of ADC scaling [V] Min: 0
CStat: CUT Datatype: Float Unit: V Def: 10
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 10
Sets value of X2 as described in P0757 (ADC scaling).
Notice:
The value x2 of ADC scaling P0759 must be greater than the value x1 of ADC scaling P0757.
P0760 Value y2 of ADC scaling Min: -99999.9
CStat: CUT Datatype: Float Unit: % Def: 100.0
P-Group: TERMINAL Active: first confirm QuickComm. No Max: 99999.9
Sets value of Y2 in [%] as described in P0757 (ADC scaling).
Dependency:
Affects P2000 to P2003 (reference frequency, voltage, current or torque) depending on which setpoint is to
be generated.
Level:
2
Level:
2
Level:
2
Level:
2