Operating instructions
04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
35
P0731 BI: Function of digital output 1
Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 52:3
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines source of digital output 1.
Common Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive warning active 0 Closed
52.8 Deviation setpoint/actual value 1 Closed
52.9 PZD control (Process Data Control) 0 Closed
52.A Maximum frequency reached 0 Closed
52.B Warning: Motor current limit 1 Closed
52.C Motor holding brake (MHB) active 0 Closed
52.D Motor overload 1 Closed
52.E Motor running direction right 0 Closed
52.F Inverter overload 1 Closed
53.0 DC brake active 0 Closed
53.1 Act. freq. f_act > P2167 (f_off) 0 Closed
53.2 Act. freq. f_act > P1080 (f_min) 0 Closed
53.3 Act. current r0027 >= P2170 0 Closed
53.4 Act. freq. f_act > P2155 (f_1) 0 Closed
53.5 Act. freq. f_act <= P2155 (f_1) 0 Closed
53.6 Act. freq. f_act >= setpoint 0 Closed
53.7 Act. Vdc r0026 < P2172 0 Closed
53.8 Act. Vdc r0026 > P2172 0 Closed
53.A PID output r2294 == P2292 (PID_min) 0 Closed
53.B PID output r2294 == P2291 (PID_max) 0 Closed
r0747 CO/BO: State of digital outputs Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Bitfields:
Bit00 Digital output 1 energized 0 NO
1 YES
Dependency:
Bit 0 = 0 :
Relay de-energized / contacts open
Bit 0 = 1 :
Relay energized / contacts closed
P0748 Invert digital outputs Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 1
Defines high and low states of relay for a given function.
Bitfields:
Bit00 Invert digital output 1 0 NO
1 YES
r0750 Number of ADCs Min: -
Datatype: U16 Unit: - Def: -
P-Group: TERMINAL Max: -
Displays number of analog inputs available.
r0751 BO: Status word of ADC Min: -
Datatype: U16 Unit: - Def: -
P-Group: TERMINAL Max: -
Displays status of analog input.
Bitfields:
Bit00 Signal lost on ADC 1 0 NO
1 YES
r0752 Act. input of ADC [V] Min: -
Datatype: Float Unit: - Def: -
P-Group: TERMINAL Max: -
Displays smoothed analog input value in volts before the characteristic block.
Level:
2
Level:
3
Level:
3
Level:
3
Level:
4
Level:
2