34 6SE6400-5BA00-0BP0
r0722 CO/BO: Binary input values Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays status of digital inputs.
Bitfields:
Bit00 Digital input 1 0 OFF
1ON
Bit01 Digital input 2 0 OFF
1ON
Bit02 Digital input 3 0 OFF
1ON
Bit03 Digital input 4 (via ADC) 0 OFF
1ON
Note:
Segment is lit when signal is active.
P0724 Debounce time for digital inputs Min: 0
CStat: CT Datatype: U16 Unit: - Def: 3
P-Group: COMMANDS Active: Immediately QuickComm. No Max: 3
Defines debounce time (filtering time) used for digital inputs.
Possible Settings:
0 No debounce time
1 2.5 ms debounce time
2 8.2 ms debounce time
3 12.3 ms debounce time
P0725 PNP / NPN digital inputs Min: 0
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: COMMANDS Active: Immediately QuickComm. No Max: 1
Switches between active high (PNP) and active low (NPN). This is valid for all digital inputs simultaneously.
The following is valid by using the internal supply:
Possible Settings:
0 NPN mode ==> low active
1 PNP mode ==> high active
Value:
NPN: Terminals 5/6/7 must be connected via terminal 9 ( 0 V).
PNP: Terminals 5/6/7 must be connected via terminal 8 (24 V).
r0730 Number of digital outputs Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays number of digital outputs (relays).
Level:
2
Level:
3
Level:
3
Level:
3