Operating instructions

MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
32 6SE6400-5BA00-0BP0
P0703 Function of digital input 3 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 9
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 3.
Possible Settings:
0 Digital input disabled
1 ON/OFF1
2 ON reverse /OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
21 Local/remote
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Details:
See P0701 (function of digital input 1).
P0704 Function of digital input 4 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 4 (via analog input).
Possible Settings:
0 Digital input disabled
1 ON/OFF1
2 ON reverse /OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase freq.)
14 MOP down (decrease freq.)
21 Local/remote
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Details:
See P0701 (function of digital input 1).
Level:
2
Level:
2