P0703 Function of digital input 3 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 9
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 3.
Possible Settings:
0   Digital input disabled
1 ON/OFF1
2   ON reverse /OFF1
3   OFF2  - coast to standstill
4   OFF3  - quick ramp-down
9   Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13  MOP up (increase frequency)
14  MOP down (decrease frequency)
15  Fixed setpoint (Direct selection)
16  Fixed setpoint (Direct selection + ON)
17  Fixed setpoint (Binary coded selection + ON)
21 Local/remote
25  DC brake enable
29 External trip
33  Disable additional freq setpoint
99  Enable BICO parameterization
Details:
See P0701 (function of digital input 1).
P0704 Function of digital input 4 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 4 (via analog input).
Possible Settings:
0   Digital input disabled
1 ON/OFF1
2   ON reverse /OFF1
3   OFF2  - coast to standstill
4   OFF3  - quick ramp-down
9   Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13  MOP up (increase freq.)
14  MOP down (decrease freq.)
21 Local/remote
25  DC brake enable
29 External trip
33  Disable additional freq setpoint
99  Enable BICO parameterization
Details:
See P0701 (function of digital input 1).
Level:
2
Level: