MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
31
P0700 Selection of command source
Min: 0
CStat: CT Datatype: U16 Unit: - Def: 2
P-Group: COMMANDS Active: first confirm QuickComm. Yes Max: 6
Selects digital command source.
Possible Settings:
0 Factory default setting
1 BOP (keypad)
2 Terminal
4 USS on BOP link
5 USS on COM link
6 CB on COM link
Note:
Changing this parameter resets (to default) all settings on item selected.
For example:
Changing form 1 to 2 resets all digital inputs to default settings.
P0701 Function of digital input 1 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 1.
Possible Settings:
0 Digital input disabled
1 ON/OFF1
2 ON reverse /OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
21 Local/remote
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Dependency:
Setting 99 (enable BICO parameterization) requires
- P0700 command source or
- P0010 = 1, P3900 = 1, 2 or 3 quick commissioning or
- P0010 = 30, P0970 = 1 factory reset in order to reset.
Notice:
Setting 99 (BICO) for expert use only.
P0702 Function of digital input 2 Min: 0
CStat: CT Datatype: U16 Unit: - Def: 12
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 99
Selects function of digital input 2.
Possible Settings:
0 Digital input disabled
1 ON/OFF1
2 ON reverse /OFF1
3 OFF2 - coast to standstill
4 OFF3 - quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (Direct selection)
16 Fixed setpoint (Direct selection + ON)
17 Fixed setpoint (Binary coded selection + ON)
21 Local/remote
25 DC brake enable
29 External trip
33 Disable additional freq setpoint
99 Enable BICO parameterization
Details:
See P0701 (function of digital input1).
Level:
1
Level:
2
Level:
2