P0100 Europe / North America Min: 0
CStat: C Datatype: U16 Unit: - Def: 0
P-Group: QUICK Active: first confirm QuickComm. Yes Max: 2
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp].
The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082)
are also set automatically here, in addition to reference frequency (P2000).
Possible Settings:
0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz
Dependency:
The setting of DIP switch 2 determines the validity of settings 0 and 1 for P0100 according to the diagram
below:
DIP2
Rem ove SDP
yes
P0100 = 2
?
no
Quick
commissioning
P0010 = 1
Power
cycle
yes
no
no
yes
no
P0100 = 0
yes
Power in kW
50 Hz
DIP2 = OFF
?
P0100 = 2
Power in kW
60 Hz
P0100 = 1
Power in hp
60 Hz
P0100 = 2
?
P0100 = 1
?
Stop drive first (i.e. disable all pulses) before you change this parameter.
P0010 = 1 (commissioning mode) enables changes to be made.
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated
motor parameters (see P0340 - calculation of motor parameters).
Notice:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see
diagram above).
Level:
1