Operating instructions
04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
19
r0071 CO: Max. output voltage
Min: -
Datatype: Float Unit: V Def: -
P-Group: CONTROL Max: -
Displays maximum output voltage.
V
max
= f(V
dc
,MOD
max
)
(Inverter)
(Motor)
r0071
V
max
Power
Field weakening
f
f
f
1
~
Flux
P,
ψ
P0304
V
n
(Motor)
P0310
f
n
(Inverter)
V
out
V
Dependency:
Actual maximum output voltage depends on the actual input supply voltage.
r0078 CO: Act. current Isq Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays component of torque generating current.
r0084 CO: Act. air gap flux Min: -
Datatype: Float Unit: % Def: -
P-Group: CONTROL Max: -
Displays air gap flux in [%] relative to the rated motor flux.
r0086 CO: Act. active current Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays active (real part) of motor current.
Dependency:
Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
Level:
3
Level:
4
Level:
4
Level: