Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
18 6SE6400-5BA00-0BP0
r0055 CO/BO: Act. control word 2 Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays additional control word of inverter and can be used to diagnose which commands are active.
Bitfields:
Bit00 Fixed frequency Bit 0 0 NO
1 YES
Bit01 Fixed frequency Bit 1 0 NO
1 YES
Bit02 Fixed frequency Bit 2 0 NO
1 YES
Bit08 PID enabled 0 NO
1 YES
Bit09 DC brake enabled 0 NO
1 YES
Bit13 External fault 1 0 YES
1NO
Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System
Parameters" in this handbook.
r0056 CO/BO: Status of motor control Min: -
Datatype: U16 Unit: - Def: -
P-Group: CONTROL Max: -
Displays status of motor control (MM420: V/f status), which can be used to diagnose inverter status.
Bitfields:
Bit00 Init. control finished 0 NO
1 YES
Bit01 Motor demagnetizing finished 0 NO
1 YES
Bit02 Pulses enabled 0 NO
1 YES
Bit03 Voltage soft start select 0 NO
1 YES
Bit04 Motor excitation finished 0 NO
1 YES
Bit05 Starting boost active 0 NO
1 YES
Bit06 Acceleration boost active 0 NO
1 YES
Bit07 Frequency is negative 0 NO
1 YES
Bit08 Field weakening active 0 NO
1 YES
Bit09 Volts setpoint limited 0 NO
1 YES
Bit10 Slip frequency limited 0 NO
1 YES
Bit11 F_out > F_max Freq. limited 0 NO
1 YES
Bit12 Phase reversal selected 0 NO
1 YES
Bit13 I-max controller active 0 NO
1 YES
Bit14 Vdc-max controller active 0 NO
1 YES
Bit15 KIB (Vdc-min control) active 0 NO
1 YES
Details:
See description of seven-segment display given in the introduction.
r0067 CO: Act. output current limit Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays valid maximum output current of inverter.
This value is influenced by P0640 (max. output current), the derating characteristics and the thermal motor
and inverter protection.
Dependency:
P0610 (motor I2t temperature reaction) defines reaction when limit is reached.
Note:
Normally, current limit = rated motor current (P0305) x motor current limit (P0640). It is less than or equal to
maximum inverter current.
The current limit may be reduced if the motor thermal model calculation indicates that overheating will
occur.
Level:
3
Level:
3
Level:
3