Operating instructions
04/02     1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
17
r0053 CO/BO: Act. status word 2
Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays second status word of inverter (in bit format).
Bitfields:
Bit00 DC brake active 0 NO
1 YES
Bit01 f_act > P2167 (f_off) 0 NO
1 YES
Bit02 f_act > P1080 (f_min) 0 NO
1 YES
Bit03 Act. current r0027 >= P2170 0 NO
1 YES
Bit04 f_act > P2155 (f_1) 0 NO
1 YES
Bit05 f_act <= P2155 (f_1) 0 NO
1 YES
Bit06 f_act>= setpoint 0 NO
1 YES
Bit07 Act. Vdc r0026 < P2172 0 NO
1 YES
Bit08 Act. Vdc r0026 > P2172 0 NO
1 YES
Bit09 Ramping finished 0 NO
1 YES
Bit10 PID output r2294 == P2292 (PID_min) 0 NO
1 YES
Bit11 PID output r2294 == P2291 (PID_max) 0 NO
1 YES
Bit14 Download data set 0 from AOP 0 NO
1 YES
Bit15 Download data set 1 from AOP 0 NO
1 YES
Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System
Parameters" in this manual.
r0054 CO/BO: Act. control word 1 Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays first control word of inverter and can be used to diagnose which commands are active.
Bitfields:
Bit00 ON/OFF1 0 NO
1 YES
Bit01 OFF2: Electrical stop 0 YES
1NO
Bit02 OFF3: Fast stop 0 YES
1NO
Bit03 Pulse enable 0 NO
1 YES
Bit04 RFG enable 0 NO
1 YES
Bit05 RFG start 0 NO
1 YES
Bit06 Setpoint enable 0 NO
1 YES
Bit07 Fault acknowledge 0 NO
1 YES
Bit08 JOG right 0 NO
1 YES
Bit09 JOG left 0 NO
1 YES
Bit10 Control from PLC 0 NO
1 YES
Bit11 Reverse (setpoint inversion) 0 NO
1 YES
Bit13 Motor potentiometer MOP up 0 NO
1 YES
Bit14 Motor potentiometer MOP down 0 NO
1 YES
Bit15 Local / Remote 0 NO
1 YES
Details:
See description of seven-segment display given in the "Introduction to MICROMASTER System
Parameters" in this manual.
Level:
2
Level:
3