Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
14 6SE6400-5BA00-0BP0
r0019 CO/BO: BOP control word Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays status of operator panel commands.
The settings below are used as the "source" codes for keypad control when connecting to BICO input
parameters.
Bitfields:
Bit00 ON/OFF1 0 NO
1 YES
Bit01 OFF2: Electrical stop 0 YES
1NO
Bit08 JOG right 0 NO
1 YES
Bit11 Reverse (setpoint inversion) 0 NO
1 YES
Bit13 Motor potentiometer MOP up 0 NO
1 YES
Bit14 Motor potentiometer MOP down 0 NO
1 YES
Note:
When BICO technology is used to allocate functions to panel buttons, this parameter displays the actual
status of the relevant command.
The following functions can be "connected" to individual buttons:
- ON/OFF1,
- OFF2,
- JOG,
- REVERSE,
- INCREASE,
- DECREASE
r0020 CO: Freq. setpoint before RFG Min: -
Datatype: Float Unit: Hz Def: -
P-Group: CONTROL Max: -
Displays actual frequency setpoint (output from ramp function generator).
r0021 CO: Act. frequency Min: -
Datatype: Float Unit: Hz Def: -
P-Group: CONTROL Max: -
Displays actual inverter output frequency (r0024) excluding slip compensation, resonance damping and
frequency limitation.
r0022 Act. filtered rotor speed Min: -
Datatype: Float Unit: 1/min Def: -
P-Group: CONTROL Max: -
Displays calculated rotor speed based on inverter output frequency [Hz] x 120 / number of poles.
Note:
This calculation makes no allowance for load-dependent slip.
r0024 CO: Act. output frequency Min: -
Datatype: Float Unit: Hz Def: -
P-Group: CONTROL Max: -
Displays actual output frequency (slip compensation, resonance damping and frequency limitation are
included).
r0025 CO: Act. output voltage Min: -
Datatype: Float Unit: V Def: -
P-Group: CONTROL Max: -
Displays [rms] voltage applied to motor.
r0026 CO: Act. filtered DC-link volt. Min: -
Datatype: Float Unit: V Def: -
P-Group: INVERTER Max: -
Displays DC-link voltage.
r0027 CO: Act. output current Min: -
Datatype: Float Unit: A Def: -
P-Group: CONTROL Max: -
Displays [rms] value of motor current [A].
Level:
3
Level:
3
Level:
2
Level:
3
Level:
3
Level:
2
Level:
2
Level:
2