MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
12 6SE6400-5BA00-0BP0
P0005 Display selection Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 21
P-Group: FUNC Active: first confirm QuickComm. No Max: 4000
Selects display for parameter r0000 (drive display).
Common Settings:
21 Actual frequency
25 Output voltage
26 DC link voltage
27 Output current
Notice:
These settings refer to read only parameter numbers ("rxxxx").
Details:
See relevant "rxxxx" parameter descriptions.
P0006 Display mode Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 2
P-Group: FUNC Active: first confirm QuickComm. No Max: 4
Defines mode of display for r0000 (drive display).
Possible Settings:
0   In Ready state alternate between setpoint and output frequency. In run display output frequency
1   In Ready state display setpoint. In run display output frequency.
2   In Ready state alternate between P0005 value and r0020 value. In run display P0005 value
3   In Ready state alternate between r0002 value and r0020 value. In run display r0002 value
4   In all states just display P0005
Note:
When inverter is not running, the display alternates between the values for "Not Running" and "Running".
Per default, the setpoint and actual frequency values are displayed alternately.
P0007 Backlight delay time Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: FUNC Active: first confirm QuickComm. No Max: 2000
Defines time period after which the backlight display turns off if no operator keys have been pressed.
Value:
P0007 = 0:
Backlight always on (default state).
P0007 = 1 - 2000:
Number of seconds after which the backlight will turn off.
P0010 Commissioning parameter Min: 0
CStat: CT Datatype: U16 Unit: - Def: 0
P-Group: ALWAYS Active: first confirm QuickComm. No Max: 30
Filters parameters so that only those related to a particular functional group are selected.
Possible Settings:
0 Ready
1 Quick commissioning
2 Inverter
29 Download
30 Factory setting
Dependency:
Reset to 0 for inverter to run.
P0003 (user access level) also determines access to parameters.
Note:
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the important
parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be entered one after
the other. The end of quick commissioning and the start of internal calculation will be done by setting P3900
= 1 - 3. Afterward parameter P0010 will be reset to zero automatically.
P0010 = 2
For service purposes only.
P0010 = 29
To transfer a parameter file via PC tool (e.g.: DriveMonitor, STARTER) parameter P0010 will be set to 29 by
the PC tool. When download has been finished PC tool resets parameter P0010 to zero.
P0010 = 30
When resetting the parameters of inverter P0010 must be set to 30. Resetting of the parameters will be
started by setting parameter P0970 = 1. The inverter will automatically reset all its parameters to their
default settings. This can prove beneficial if you experience problems during parameter setup and wish to
start again. Duration of factory setting will take about 60 s.
If P3900 is not 0 (0 is the default value), this parameter is automatically reset to 0.
Level:
2
Level:
3
Level:
3
Level:
1