Operating instructions
04/02     1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
11
1.3 Parameter Description
Note:
Level 4 Parameters are not visible with BOP or AOP.
r0000 Drive display Min: -
Datatype: U16 Unit: - Def: -
P-Group: ALWAYS Max: -
Displays the user selected output as defined in P0005.
Note:
Pressing the "Fn" button for 2 seconds allows the user to view the values of DC link voltage, output
frequency, output voltage, output current, and chosen r0000 setting (defined in P0005).
r0002 Drive state Min: -
Datatype: U16 Unit: - Def: -
P-Group: COMMANDS Max: -
Displays actual drive state.
Possible Settings:
0   Commissioning mode (P0010 != 0)
1   Drive ready
2   Drive fault active
3   Drive starting (DC-link precharging)
4   Drive running
5   Stopping (ramping down)
Dependency:
State 3 visible only while precharging DC link, and when externally powered communications board is fitted.
P0003 User access level Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 1
P-Group: ALWAYS Active: first confirm QuickComm. No Max: 4
Defines user access level to parameter sets. The default setting (standard) is sufficient for most simple
applications.
Possible Settings:
0   User defined parameter list - see P0013 for details on use
1   Standard: Allows access into most frequently used parameters.
2   Extended: Allows extended access e.g. to inverter I/O functions.
3   Expert: For expert use only.
4   Service: Only for use by authorized service personal - password protected.
P0004 Parameter filter Min: 0
CStat: CUT Datatype: U16 Unit: - Def: 0
P-Group: ALWAYS Active: first confirm QuickComm. No Max: 22
Filters available parameters according to functionality to enable a more focussed approach to
commissioning.
Possible Settings:
0   All parameters
2 Inverter
3 Motor
7   Commands, binary I/O
8   ADC and DAC
10  Setpoint channel / RFG
12 Drive features
13 Motor control
20 Communication
21  Alarms / warnings / monitoring
22  Technology controller (e.g. PID)
Example:
P0004 = 22 specifies that only PID parameters will be visible.
Dependency:
Parameters marked "Quick Comm: Yes" in the parameter header can only be set when P0010 = 1 (Quick
Commissioning).
Level:
1
Level:
2
Level:
1
Level:
1