MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
104 6SE6400-5BA00-0BP0
r2250 CO: Output setpoint of PID-MOP Min: -
Datatype: Float Unit: % Def: -
P-Group: TECH Max: -
Displays output setpoint of motor potentiometer in [%].
Note:
r2250 = 100 % corresponds to 4000 hex
P2253 CI: PID setpoint Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 0:0
P-Group: TECH Active: first confirm QuickComm. No Max: 4000:0
Defines setpoint source for PID setpoint input.
PID
MOP
ADC
PID
SUM
PID
PID
FF
USS
BOP link
USS
COM link
CB
COM link
P2254
P2253
PID
RFG
PID
PT1
0
1
−
∆
PID
P2200
P2264
PID
PT1
PID
SCL
Output
PID
Motor
control
This parameter allows the user to select the source of the PID setpoint. Normally, a digital setpoint is
selected either using a fixed PID setpoint or an active setpoint.
Common Settings:
755 = Analog input 1
2224 = Fixed PI setpoint (see P2201 to P2207)
2250 = Active PI setpoint (see P2240)
P2254 CI: PID trim source Min: 0:0
CStat: CUT Datatype: U32 Unit: - Def: 0:0
P-Group: TECH Active: first confirm QuickComm. No Max: 4000:0
Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the PID setpoint.
Common Settings:
755 = Analog input 1
2224 = Fixed PI setpoint (see P2201 to P2207)
2250 = Active PI setpoint (see P2240)
P2255 PID setpoint gain factor Min: 0.00
CStat: CUT Datatype: Float Unit: - Def: 100.00
P-Group: TECH Active: Immediately QuickComm. No Max: 100.00
Gain factor for PID setpoint. The PID setpoint input is multiplied by this gain factor to produce a suitable
ratio between setpoint and trim.
P2256 PID trim gain factor Min: 0.00
CStat: CUT Datatype: Float Unit: - Def: 100.00
P-Group: TECH Active: Immediately QuickComm. No Max: 100.00
Gain factor for PID trim. This gain factor scales the trim signal, which is added to the main PID setpoint.