Operating instructions
MM420 Parameter List 04/02
MICROMASTER 420 Parameter List
102 6SE6400-5BA00-0BP0
P2206 Fixed PID setpoint 6 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 50.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 6
Details:
See P2201 (Fixed PID Setpoint 1).
P2207 Fixed PID setpoint 7 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 60.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 7
Details:
See P2201 (Fixed PID Setpoint 1).
P2216 Fixed PID setpoint mode - Bit 0 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm. No Max: 3
Fixed frequencies for PID setpoint can be selected in three different modes. Parameter P2216 defines the
mode of selection Bit 0.
Possible Settings:
1 Direct selection
2   Direct selection + ON command
3   Binary coded selection + ON command
P2217 Fixed PID setpoint mode - Bit 1 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm. No Max: 3
BCD or direct selection Bit 1 for PID setpoint.
Possible Settings:
1 Direct selection
2   Direct selection + ON command
3   Binary coded selection + ON command
P2218 Fixed PID setpoint mode - Bit 2 Min: 1
CStat: CT Datatype: U16 Unit: - Def: 1
P-Group: TECH Active: first confirm QuickComm. No Max: 3
BCD or direct selection Bit 2 for PID setpoint.
Possible Settings:
1 Direct selection
2   Direct selection + ON command
3   Binary coded selection + ON command
P2220 BI: Fixed PID setp. select Bit 0 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 0
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
722.3 = Digital input 4 (via analog input, requires P0704 to be set to 99)
P2221 BI: Fixed PID setp. select Bit 1 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 1.
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)
P2222 BI: Fixed PID setp. select Bit 2 Min: 0:0
CStat: CT Datatype: U32 Unit: - Def: 0:0
P-Group: COMMANDS Active: first confirm QuickComm. No Max: 4000:0
Defines command source of fixed PID setpoint selection Bit 2
Common Settings:
722.0 = Digital input 1 (requires P0701 to be set to 99, BICO)
722.1 = Digital input 2 (requires P0702 to be set to 99, BICO)
722.2 = Digital input 3 (requires P0703 to be set to 99, BICO)