Operating instructions

04/02 1 Parameters
MICROMASTER 420 Parameter List
6SE6400-5BA00-0BP0
101
P2201 Fixed PID setpoint 1
Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 0.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 1
In addition, you can set any of the digital input parameters to fixed PID setpoint (FF-PID) via the digital
inputs (P0701 - P0703).
There are three selection modes for the PID fixed setpoint:
1 Direct selection (P0701 = 15 or P0702 = 15, etc):
In this mode of operation, 1 digital input selects one PID fixed setpoint.
2 Direct selection with ON command (P0701 = 16 or P0702 = 16, etc.):
Description as for 1), except that this type of selection issues an ON command concurrent with any setpoint
selection.
3 Binary Coded Decimal selection (P0701 - P0703 = 17):
Using this method to select the fixed PID setpoint (FF-PID) allows you to choose up to 7 different PID
setpoints.
The setpoints are selected according to the following table:
Example:
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Inactive
Active
ActiveActive
Active
Active
Active
Active
Active
Active
Active
Active
Active
Inactive
Inactive
Inactive
Inactive
DIN3 DIN2 DIN1
OFF
P2201 PID-FF1
P2202 PID-FF2
P2203 PID-FF3
P2204 PID-FF4
P2205 PID-FF5
P2206 PID-FF6
P2207 PID-FF7
Dependency:
P2000 = 1 required in user access level 2 to enable setpoint source.
In mode 1 (above):
ON command required to start motor (enable pulses).
In mode 2 (above):
If inputs programmed to PID fixed setpoint and selected together, the selected setpoints are summed.
Note:
You may mix different types of frequencies; however, remember that they will be summed if selected
together.
P2201 = 100 % corresponds to 4000 hex
P2202 Fixed PID setpoint 2 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 10.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 2
Details:
See P2201 (Fixed PID Setpoint 1).
P2203 Fixed PID setpoint 3 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 20.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 3
Details:
See P2201 fixed PID setpoint 1 (FF-PID 1).
P2204 Fixed PID setpoint 4 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 30.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 4
Details:
See P2201 (Fixed PID Setpoint 1).
P2205 Fixed PID setpoint 5 Min: -130.00
CStat: CUT Datatype: Float Unit: % Def: 40.00
P-Group: TECH Active: Immediately QuickComm. No Max: 130.00
Defines Fixed PID Setpoint 5
Details:
See P2201 (Fixed PID Setpoint 1).
Level:
2
Level:
2
Level:
2
Level:
2
Level:
2