Operating instructions
International English 5. SYSTEM PARAMETERS
76 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
P1210 Automatic restart
Enables restart after a mains break or after a fault.
Possible settings:
0 = Disabled
1 = Acknowledges faults on power up – inverter is not started. It is
necessary to toggle the ON command to start the inverter.
2 = Restart after mains break (blackout) / power on
3 = Restart after fault/mains break (blackout / brownout)
4 = Restart after mains break (blackout / brownout)
5 = Restart after mains break/fault, ignoring previous history
Warning:
Setting 2 to 5 can cause the motor to restart unexpectedly!
Note
Auto restart will only work if the ON command remains constantly present. E.g. via a digital
input wire link.
If the motor could still be turning or is possibly still being driven by the load, flying restart
must also be enabled (P1200).
0
5
[1]
-
2
12
‘•’
Holding brake profile enableP1215
Enables/disables holding brake function
You can use this function to make the inverter follow the profile below. It is also possible to
have a relay switch at point 1 and point 2 if programmed in P0731 = 52.C to control a brake.
f min
(P1080)
Point 1 Point 2
P1217P1216
Possible settings:
0 = Disabled
1 = Enabled
Note
The brake relay opens at Point 1 if enabled using P0731. The brake relay closes at Point 2.
0
1
[0]
-
2
12
Holding brake release delayP1216
Defines the time at which the inverter runs at f
min
before ramping up at point 1 (as shown in
P1215 diagram).
0
20
[1]
s
2
12