International English 5. SYSTEM PARAMETERS
74 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
P1134 Rounding type
Defines continuous smoothing (default) or discontinuous smoothing as a response to OFF
commands or setpoint reduction.
The total smoothing time must be set > 0s; otherwise this parameter will have no effect.
Possible settings:
0 = Continuous
1 = Discontinuous
TimeStop
freq
0
Discontinuous
Continuous
0
1
[0]
-
2
10
‘•’