Operating instructions
5. SYSTEM PARAMETERS International English
MICROMASTER 420 Operating Instructions 69
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
P1004 Fixed frequency 4
Defines fixed frequency setpoint 4
See description for P1001
-650
650
[15]
Hz
2
10
‘•’
Fixed frequency 5P1005
Defines fixed frequency setpoint 5
See description for P1001
-650
650
[20]
Hz
2
10
‘•’
Fixed frequency 6P1006
Defines fixed frequency setpoint 6
See description for P1001
-650
650
[25]
Hz
2
10
‘•’
Fixed frequency 7P1007
Defines fixed frequency setpoint 7
See description for P1001
-650
650
[30]
Hz
2
10
‘•’
Setpoint memory of Keypad (Motor potentiometer)P1031
Saves the last keypad (Motor potentiometer) setpoint that was active before OFF command
or power down.
Possible settings:
0= Not saved
1 = Saved (P1040 is updated).
Note:
On next ON command, keypad (Motor potentiometer) setpoint will be the saved value in
P1040
0
1
[0]
-
2
10
‘•’
Inhibit reverse direction of Keypad (Motor potentiometer)P1032
Inhibits the reverse setpoint selection when keypad (Motor potentiometer) is chosen either
as main setpoint or additional setpoint (using P1000)
Possible Settings:
0 Reverse direction is allowed – it is possible to change motor direction using the
keypad (Motor potentiometer) setpoint (increase / decrease frequency either by using
digital inputs or keypad up / down buttons)
1 Reverse direction inhibited
0
1
[1]
-
2
10