P1001 Fixed frequency 1
Defines fixed frequency setpoint 1
How to use fixed frequencies;
To use fixed frequencies it is necessary to select fixed frequency operation using P1000.
Fixed frequencies can be selected using the digital inputs, and can also be combined with
an ON command.
There are three types of Fixed Frequencies.
1) Direct selection
2) Direct selection + ON command
3) Binary Coded selection + ON command
1. Direct selection (P0701 – P0703 = 15)
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are
active together, the selected frequencies are summed. E.g. (FF1 + FF2 + FF3).
Note:
An ON command is also required to start the inverter e.g. from keypad or serial link etc.
2. Direct selection + ON command (P0701 – P0703 = 16)
This fixed frequency selection combines the fixed frequencies with an ON command.
In this mode of operation 1 digital input selects 1 fixed frequency. If several inputs are
active together, the selected frequencies are summed. E.g. (FF1 + FF2 + FF3).
3. Binary Coded Selection + ON command (P0701 – P0703 = 17)
Up to 7 fixed frequencies can be selected using this method. The fixed frequencies are
selected according to the following table:
DIN3 DIN2 DIN1
OFF Inactive Inactive Inactive
P1001 FF1 Inactive Inactive
Active
P1002 FF2 Inactive
Active
Inactive
P1003 FF3 Inactive
Active Active
P1004 FF4
Active
Inactive Inactive
P1005 FF5
Active
Inactive
Active
P1005 FF6
Active Active
Inactive
P1007 FF7
Active Active Active
-650
650
[0]
Hz
2
10
‘
•’
Fixed frequency 2P1002
Defines fixed frequency setpoint 2
See description for P1001
-650
650
[5]
Hz
2
10
‘
•’
Fixed frequency 3P1003
Defines fixed frequency setpoint 3
See description for P1001
-650
650
[10]
Hz
2
10
‘
•’