Operating instructions
International English 5. SYSTEM PARAMETERS
64 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
P0771 Analog output function
Defines function of the 0 –20 mA analog output.
Possible settings:
These are the most common values:
21 Actual frequency (scaled to P2000)
24 Output frequency (scaled to P2000)
25 Output voltage (scaled to 1000 V)
26 DC link voltage (scaled to 1000 V)
27 Output current (scaled to P2002 Level 3)
Other values: See individual parameter descriptions
0
2248.0
[21]
-
2
8
‘•’
Analog output valuer0774
Shows the value of the analog output in mA.
-
-
[-]
%
2
8
Value X1 of analog output characteristicsP0777
Defines the x1 output characteristic.
The parameters P0777 – P0780 work as follows:
Output signal (mA)
0
20
20 mA
P0780 Y2
P0778 Y1
P0777
X1
P0779
X2
100%
(-100%)
Points (x1, y1) , (x2,y2) can be chosen freely
-99999
99999
[0]
%
2
8
‘•’
Value Y1 of analog output characteristicsP0778
Defines y1 of output characteristic
0
4
[0]
-
2
8
‘•’
Value X2 of analog output characteristicsP0779
Defines x2 of output characteristic
-99999
99999
[100]
%
2
8
‘•’
Value Y2 of analog output characteristicsP0780
Defines y2 of output characteristic
0
20
[20]
-
2
8
‘•’
Analog output deadbandP0781
Sets the width of a dead-band in mA for the analog output.
0
20
[0]
-
2
8
'•'