♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
P0614 Motor I
2
t overload warning level
The motor I
2
t calculation estimates the duration for which the motor can be overloaded
without overheating. When the maximum allowed period has been reached the motor I
2
t
calculation is 100% (see r0034). This parameter defines the calculated I
2
t value in % at
which a warning (A0511) is generated.
Note:
A motor over-temperature trip (F0011) is produced at 110% of this level.
0
400
[100]
%
2
3
‘•’
Motor overload factor (%)P0640
Defines instantaneous motor current limit as a % of the nominal motor current. This value
is limited to 150% of nominal inverter current (r0207) or to 400% of the motor current
(whichever is the lower).
0
400
[150]
%
2
3
‘•’
Selection of command sourceP0700
Parameter for selecting the digital command source. When the parameter is changed, all
digital input parameters will be set to reasonable values.
Possible Settings
0 "Factory default setting"
1 "keypad" (BOP/AOP)
2 "Terminal"
4 "USS1 on BOP-Link" (RS-232)
5 "USS2 on Comm-Link" (RS-485)
6 "PROFIBUS / Fieldbus on Comm-Link"
Note:
Changing this parameter resets the settings to default on the item selected e.g. if you
change from setting 1 to setting 2, all digital inputs will now have default settings
0
6
[0]
-
1
7
Function of digital input 1P0701
Selects function of digital input 1
0 Digital input disabled
1 ON Right
2 ON Left" (ON + Reverse)
3 OFF2 – coast to standstill
4 OFF3 – Quick ramp down (P1135 defines ramp down time)
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 Increase frequency (Main/additional setpoint=Keypad (P1000))
14 Decrease frequency (Main or additional setpoint = Keypad)
15 Fixed frequency 1 (see P1001)
16 Fixed frequency 1 + ON (see P1001)
17 Fixed frequencies 1 to 7 (Binary Coded) (see P1001)
25 DC brake enable (see P1230 to P1233)
29 External trip
33 Disable additional setpoint (defined in P1000)
99 Enable BICO parameterization – for expert use only
Can only be reset via P0700 or P3900 = 1, 2 or factory setting P0970 = 1
0
99
[1]
-
2
7