Operating instructions
International English 5. SYSTEM PARAMETERS
54 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
♦
♦♦
♦P0003 User
Access Level
♦
♦♦
♦P0004 Setting
♦
♦♦
♦Changeable
♦
♦♦
♦Status
Inverter current rating
r0207
Displays the maximum continuous output current of the inverter.
-
-
[-]
A
2
2
Nominal inverter input voltager0208
Displays nominal AC supply voltage of the inverter.
Possible values:
230 = 200-240V ± 10%
400 = 400-480V ± 10%
-
-
[-]
V
2
2
Select motor typeP0300
Selects motor type.
Possible settings:
1 = Asynchronous motor.
2 = Synchronous motor.
Note 1:
This parameter can only be changed when P0010=1
This parameter is required during commissioning to select motor type and optimize inverter
performance. Most motors are asynchronous; if in doubt, use the formula below.
(P0310 x 60) / P0311
If the result is a whole number, the motor is synchronous.
Note 2:
If synchronous motor is selected, the following functions are not available: Power Factor
(P0308), Motor efficiency (P0309), magnetization time (P0346, Level 3), demagnetization
time (P0347, Level 3), flying restart (P1200, P1202, Level 3, P1203, Level 3), DC braking
(P1230, Level 3, P1232, P1233), slip compensation (P1335), slip limit (P1336).
1
2
[1]
-
2
3
‘
’
Rated motor voltageP0304
Nominal motor voltage (V) from rating plate.
Following diagram show you where to find the motor data from your motor.
P0307
3~Mot
1LA7130-4AA10
EN 60034
Cos ϕ
ϕϕ
ϕ=
==
=0.81
50 Hz
1455/min
5.5kW 19.7/11.A
230-400 V
Cos ϕ
ϕϕ
ϕ=
==
=0.82
60 Hz
6.5kW
460 V
10.9 A
1755/min
No UD 0013509-0090-0031 TICI F 1325 IP 55 IM B3
Υ
ΥΥ
Υ=
==
=440-480
11.1-11.3 A
45kg
==
====
==∆/Υ
∆/Υ∆/Υ
∆/Υ=
==
=220-240/380-420 V
19.7-20.6/11.4-11.9 A
P0311
P0308
P0304P0305
P0310
95.75%
P0309
P0344
Note:
This parameter can only be changed when P0010=1.
10
2000
[
***]
V
1
3
‘
’