Operating instructions

International English 5. SYSTEM PARAMETERS
52 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
r0053 Status word 2
This parameter displays the second status word of the inverter (in bit format). It can be
used to diagnose the status of the inverter by referring to the information given in the
Introduction.
Possible values:
Bit 0 DC brake active 0 NO
1YES
Bit 1 Inverter frequency < switch off limit 0 YES
1NO
Bit 2 Inverter frequency < minimum frequency 0 YES
1NO
Bit 3 Current limit 0 NO
1YES
Bit 4 Actual frequency > reference frequency 0 NO
1YES
Bit 5 Actual frequency < reference frequency 0 NO
1YES
Bit 6 Actual frequency setpoint 0 NO
1YES
Bit 7 Voltage < threshold 0 NO
1YES
Bit 8 Voltage > threshold 0 NO
1YES
Bit 9 reserve 0 NO
1YES
Bit A PI frequency < threshold 0 NO
1YES
Bit b PI saturation 0 NO
1YES
-
-
[-]
-
2
7