Operating instructions

International English 3. COMMISSIONING
32 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Changing parameters with the BOP
The following description shows how to change the parameter P1082, use this
description as a guide for setting any parameters using the ‘BOP’.
Step Result on display
1
Press to access parameters
2
Press
until P0010 is displayed
3
Press to access P0010 parameter
value level
4
Press
to set P0010 = 1
5
Press
to save and exit parameter
value level
6
Press
until P1082 is displayed
7
Press
to access P1082 parameter
value level
8
Press to select desired maximum
frequency
9
Press
to save and exit parameter
value level
10 Press to return to P0010
11
Press to access P0010 parameter
value level
12
Press
to return value to P0010 = 0
13
Press
to save and exit parameter
value level
14
Press
to return to r0000
15
Press to exit Parameterization
The LCD will alternate between actual
frequency and the requested frequency
setpoint
Figure 3-4 Changing parameters via the BOP
The required maximum frequency has now been stored.
Note - Busy Message
In some cases - when changing parameter values - the display on the BOP shows
" - - - -". This means the inverter is busy with tasks of higher priority.