Input voltage range 3 AC 380 V – 480 V, ± 10 %
(with built in Class A Filter)
Order No. 6SE6420-
2AD22-
2BA0
2AD23-
0BA0
2AD24-
0BA0
2AD25-
5CA0
2AD27-
5CA0
2AD31-
1CA0
[kW]
2,2 3,0 4,0 5,5 7,5 11,0
Motor Output Rating
[hp]
3,0 4,0 5,0 7,5 10,0 15,0
Output Power [kVA]
4,5 5,9 7,8 10,1 14,0 19,8
Output Current Max. [A]
5,9 7,7 10,2 13,2 18,4 26,0
Input Current [A]
7,5 10 12,8 17,3 23,1 33,8
16 16 20 20 25 35
Recommended Fuse [A]
3NA3805 3NA3805 3NA3807 3NA3807 3NA3810 3NA3814
[mm
2
]
1,0 1,0 1,5 2,5 4,0 6,0
Input Cable Min.
[awg]
17 17 15 13 11 9
[mm
2
]
6,0 6,0 6,0 10,0 10,0 10,0
Input Cable Max.
[awg]
999777
[mm
2
]
1,0 1,0 1,0 1,5 2,5 4,0
Output Cable Min.
[awg]
17 17 17 15 13 11
[mm
2
]
6,0 6,0 6,0 10,0 10,0 10,0
Output Cable Max.
[awg]
999777
[kg]
3,1 3,3 3,3 5,4 5,7 5,7
Weight
[lbs]
6,8 7,3 7,3 11,9 12,5 12,5
w [mm]
149,0 149,0 149,0 185,0 185,0 185,0
h [mm]
202,0 202,0 202,0 245,0 245,0 245,0
d [mm]
172,0 172,0 172,0 195,0 195,0 195,0
w [inches]
5,87 5,87 5,87 7,28 7,28 7,28
h [inches]
7,95 7,95 7,95 9,65 9,65 9,65
Dimensions
d [inches]
6,77 6,77 6,77 7,68 7,68 7,68