Operating instructions

Issue B1 7 MICROMASTER 420 specifications
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
77
Table 7-3 MICROMASTER 420 Specifications
In order to have a UL compliant installation fuses from the SITOR range with the
appropriate current rating must be used.
Input voltage range 1 AC 200 V – 240 V, ± 10 %
(with built in Class A Filter)
Order No. 6SE6420-
2AB11-
2AA0
2AB12-
5AA0
2AB13-
7AA0
2AB15-
5AA0
2AB17-
5AA0
2AB21-
1BA0
2AB21-
5BA0
2AB22-
2BA0
2AB23-
0CA0
[kW]
0,12 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3,0
Motor Output Rating
[hp]
0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0
Output Power [kVA]
0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0
Output Current Max. [A]
0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6
Input Current [A]
2 4 5,5 7,5 9,9 14,4 19,6 26,4 35,5
10 10 10 10 16 20 20 25 32
Recommended Fuse [A]
3NA3803 3NA3803 3NA3803 3NA3803 3NA3805 3NA3807 3NA3807 3NA3810 3NA3812
[mm
2
]
1,0 1,0 1,0 1,0 1,0 2,5 2,5 4,0 6,0
Input Cable Min.
[awg]
17 17 17 17 17 17 15 11 9
[mm
2
]
2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0
Input Cable Max.
[awg]
13 13 13 13 13 9 9 9 7
[mm
2
]
1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5
Output Cable Min.
[awg]
17 17 17 17 17 17 17 17 15
[mm
2
]
2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0
Output Cable Max.
[awg]
13 13 13 13 13 9 9 9 7
[kg]
1,2 1,2 1,2 1,3 1,3 3,3 3,6 3,6 5,2
Weight
[lbs]
2,6 2,6 2,6 2,9 2,9 7,3 7,9 7,9 11,4
w [mm]
73,0 73,0 73,0 73,0 73,0 149,0 149,0 149,0 185,0
h [mm]
173,0 173,0 173,0 173,0 173,0 202,0 202,0 202,0 245,0
d [mm]
149,0 149,0 149,0 149,0 149,0 172,0 172,0 172,0 195,0
w [inches]
2,87 2,87 2,87 2,87 2,87 5,87 5,87 5,87 7,28
h [inches]
6,81 6,81 6,81 6,81 6,81 7,95 7,95 7,95 9,65
Dimensions
d [inches]
5,87 5,87 5,87 5,87 5,87 6,77 6,77 6,77 7,68