Operating instructions
Issue B1 5 System parameters
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
63
Motor Control (P0004 = 13)
Par. No. Parametername Default Acc WS QC
r0020 CO: Act. frequency setpoint - 3 - -
r0021 CO: Act. frequency - 2 - -
r0022 Act. rotor speed 3 N - -
r0024 CO: Act. output frequency - 3 - -
r0025 CO: Act. output voltage - 2 - -
r0027 CO: Act. output current - 2 - -
r0034[1] CO: Motor utilization - 2 - -
r0036 CO: Drive utilization - 4 - -
r0056 CO/BO: Status of motor control - 2 - -
r0067 CO: Act. drive current limit - 3 - -
r0071 CO: Max. output voltage - 3 - -
r0078 CO: Act. current Isq - 4 - -
r0084 CO: Act. Air gap flux - 4 - -
r0086 CO: Act. active current - 3 - -
P1300[1] Control mode 1 2 CT Q
P1310[1] Continuous boost 50.0 2 CUT -
P1311[1] Acceleration boost 0.0 2 CUT -
P1312[1] Starting boost 0.0 2 CUT -
r1315 CO: Total boost voltage - 4 - -
P1316[1] Boost end frequency 20.0 3 CUT -
P1320[1] Programmable V/f freq. coord. 1 0.00 3 CT -
P1321[1] Programmable V/f volt. coord. 1 0.0 3 CUT -
P1322[1] Programmable V/f freq. coord. 2 0.00 3 CT -
P1323[1] Programmable V/f volt. coord. 2 0.0 3 CUT -
P1324[1] Programmable V/f freq. coord. 3 0.00 3 CT -
P1325[1] Programmable V/f volt. coord. 3 0.0 3 CUT -
P1333 Start frequency for FCC 10.0 3 CUT -
P1335 Slip compensation 0.0 2 CUT -
P1336 Slip limit 250 2 CUT -
r1337 CO: Slip frequency - 3 - -
P1338 Resonance damping gain V/f 0.00 3 CUT -
P1340 Imax controller prop. gain 0.000 3 CUT -
P1341 Imax controller integral time 0.300 3 CUT -
r1343 CO: Imax controller freq. output - 3 - -
r1344 CO: Imax controller volt. output - 3 - -
P1350[1] Voltage soft start 0 3 CUT -