Operating instructions

Issue B1 4 Using the MICROMASTER 420
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
51
4.4 Control modes (P1300)
All control modes of the MICROMASTER 420 are based on a V/Hz control. The
following different control variants are provided to suit different types of application:
Ø Linear V/f control, P1300 = 0
Can be used for variable and constant torque applications, such as conveyors
and positive displacement pumps.
Ø Linear V/f control with Flux Current Control (FCC) P1300 = 1
This control mode can be used to improve the efficiency and dynamic
response of the motor.
Ø Quadratic V/f control P1300 = 2
This mode can be used for variable torque loads, such as fans and pumps.
Ø Multi-point V/f control P1300 = 3
For information regarding this mode of operation, please consult the MM420
Reference Manual.