Operating instructions
Issue B1 4 Using the MICROMASTER 420
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
49
4.2 Command sources (P0700)
NOTICE
The ramp times and ramp-smoothing functions also affect how the motor starts
and stops. For details of these functions, please refer to parameters P1120, P1121,
P1130 – P1134 in the Parameter List.
Starting the motor
Ø Standard Terminal 5 (DIN1, high)
Ø Options see P0700 to P0704
Stopping the motor
There are several ways to stop the motor:
Ø Standard:
♦ OFF1 (4.3.1) Terminal 5 (DIN1, low)
♦ OFF2 (4.3.2) Off button on BOP/AOP, pressing the Off button once long
(two seconds) or twice (with default settings not possible
without BOP/AOP)
♦ OFF3 (4.3.3) Not active in the default (factory) setting
Ø Options see P0700 to P0704
Reversing the motor
Ø Standard Terminal 6 (DIN2, high)
Ø Options see P0700 to P0704
4.3 OFF and braking functions
4.3.1 OFF1
This command (produced by canceling the ON command) causes the inverter to
come to a standstill at the selected ramp-down rate.
Parameter to change ramp time see P1121
NOTICE
Ø ON and the following OFF1 command must have the same source.
Ø If the ON/OFF1 command is set to more than one Digital input, only the last set
Digital Input is number e.g. DIN3 is active.
Ø OFF1 can be combined with DC braking or Compound braking