Operating instructions
3 Commissioning Issue B1
MICROMASTER 420 Operating Instructions
38 6SE6400-5AA00-0BP0
3.2.2.1 Commissioning with the BOP
You can alter parameter values via the BOP. To set
parameters on this panel, you must remove the SDP and
attach the BOP (see Appendix 0).
The BOP features a five-digit, seven-segment display for
showing parameter numbers and values, alarm and fault
messages and setpoints and actual values. Parameter
information cannot be saved via the BOP.
Table 3-2 shows the factory default settings for operation
via the BOP.
NOTICE
♦ The BOP motor control functions are disabled by default. To control the motor
via the BOP, parameter P0700 should be set to 1 and P1000 set to 1.
♦ The BOP can be fitted to and removed from the inverter whilst power is
applied.
♦ If the BOP has been set as the I/O control (P0700 = 1), the drive will stop if
the BOP is removed.
Table 3-2 Default settings for operation using the BOP
Parameter Meaning Default Europe (North America)
P0100 Operating Mode Europe/US 50 Hz, kW (60Hz, hp)
P0307 Power (rated motor) kW (Hp)
P0310 Motor frequency rating 50 Hz (60 Hz)
P0311 Motor speed rating 1395 (1680) rpm [depending on variant]
P1082 Maximum Motor Frequency 50 Hz (60 Hz)